How much light does a room need? Lux, lumens and luminaire quantities
EV Sun team · 14/11/2026 · 5 min read
A practical lighting selection guide: illuminance for kitchens, offices and warehouses, and how to calculate luminaire quantities.

Lighting selection starts with what people do in the room. A corridor, kitchen worktop and desk each need a different amount of light. Lamp wattage alone is not enough to compare products. You need to know their luminous flux and the illuminance required on the working surface.
The EV Sun Lighting calculator helps you make an initial estimate. Enter the room type and dimensions, and the tool compares luminaire variants. The result is a starting point for selection. It does not replace a lighting design that checks layout, uniformity and glare for the specific space.
Lumens, lux and watts
Lumens (lm) express luminous flux: the amount of light emitted by a luminaire. Lux (lx) expresses illuminance on a surface. One lux is one lumen per square metre. Watts (W) express power consumption. Of these three values, only watts directly indicate energy use while the light is on.
Compare power and luminous flux separately. Two luminaires with similar wattages may provide different amounts of light. Colour temperature, expressed in kelvins, is no substitute for lumen data either. Choose the colour temperature to suit the interior, and the number and layout of luminaires to provide the light needed on its surfaces.
Starting points for selection
- Corridors and entrance halls: approximately 100 lx.
- Living rooms and bedrooms: 150–200 lx, recommended values for homes.
- Domestic kitchens and bathrooms: approximately 300 lx, recommended values for homes.
- Offices: 500 lx on the working surface.
- Classrooms: 500 lx, UGR ≤ 19, Ra ≥ 80 (EN 12464-1:2021).
- Warehouses: 100–200 lx, depending on the tasks performed.
Assess workplace values against EN 12464-1:2021, and treat the stated domestic values as recommendations. A room name does not describe every task carried out there. For a building with different workstations, consider the actual activities rather than applying a single figure throughout.
Estimating the luminous flux required
In the simplified method, multiply the required illuminance by the floor area, then divide by the utilisation and maintenance factors. These account for light that does not reach the working plane and for the effect of operating conditions on lighting levels. This is an estimate, not a measurement of the completed installation.
Calculation example: an 8 × 6 m office has a floor area of 48 m². At 500 lx, using an assumed combined factor of 0.5, the required flux is 48,000 lm. The EVLN‑PL2X4-72W-5CCT panel has a specified maximum luminous flux of 8,640 lm. Six panels provide a total of 51,840 lm before installation conditions are taken into account.
This is not a recommendation to use six panels in every office of that size. The example shows the calculation method only. The design must also check mounting height, spacing, interior surfaces and the selected luminaire setting. A variant with adjustable wattage does not always operate at its maximum value.
Calculator assumptions
Calculations are indicative, based on EN 12464-1:2021 for workplaces, with recommended values for homes. A general utilisation factor is used rather than one derived from a photometric file. The result therefore does not by itself confirm compliance of the whole installation or the distribution of light at every point in the room.
The calculator selects luminaires. GU10 bulbs and T8 LED tubes are light sources used within other luminaires. Use LED replacements to compare replacement options for these sources. The lumen output of a light source alone does not fully describe the light distribution of an installation.
Uniformity and glare
Average illuminance does not show whether darker areas will occur between luminaires. Lighting uniformity is expressed by U₀. The calculator’s indicative spacing helps organise the layout, but U₀ is checked in a DIALux design. Following a spacing guideline is not a measurement of uniformity.
The same applies to UGR. When a result shows a required UGR, always read it with the note: check in the lighting design. We do not automatically assign every panel a particular glare value for any interior. The entire lighting layout matters, not just the luminaire family or wattage.
Preparing information for a lighting design
Record the room’s length, width and height, and the work carried out there. Specify the ceiling, proposed mounting locations and any damp or dust. Luminaire selection narrows down the product family. Compare EVLN‑PL panels with EVLN‑SDL surface-mounted and EVLN‑DL recessed luminaires on their product pages.
For a whole building, add further rooms to your schedule in the Lighting calculator. Give them names you can recognise on the floor plan, such as office or meeting room. Send the schedule and floor plans through Contact. We will prepare a DIALux lighting design and luminaire quote free of charge.
Keep the full variant codes in the schedule. A family name, such as LED panel, does not identify the selected wattage or luminous flux. The code lets you compare the calculator result with the product datasheet and quote without confusing different versions.
Frequently asked questions
Does higher wattage tell me how much light I need? Do not compare products by watts alone. Check the luminous flux in lumens, then the required illuminance in lux and the layout conditions in the specific room.
Does the calculator confirm UGR and uniformity? No. These requirements need checking in the lighting design. The lumen method helps estimate luminaire quantities and prepare information for further selection.
What if I do not know the luminaire model? Start with Luminaire selection, then move to the Lighting calculator. For a building project, prepare floor plans and workstation descriptions, and contact us.